Connected load w
connected_load_w
Sum of source-owned wayside device loads
Scores if within ±3% of the reference value.
Calculates deterministic SSC-02 wayside cabinet resilience metrics from a task-owned synthetic source pack. The template combines connected load, design load, backup energy, battery capacity margin, 48 V feeder voltage drop, optical link budget, UPS sizing, and an overall synthetic pass score.
with-tool: The model is given an executable Python calculator script.
Standards
One template produces many comparable benchmark tasks while keeping the scoring contract fixed.
01
The reusable contract shown on this page.
02
An archetype and site context are sampled.
03
Inputs may be hidden at harder tiers.
04
The model responds with the declared outputs.
Inputs the model receives, and the outputs it is scored on.
25 inputs
Included directly in every task prompt.
Signal processor
signal_processor_w
LOAD-02-DEVICE-07 signal processor load
Axle counter
axle_counter_w
LOAD-02-DEVICE-07 axle counter load
Comms switch
comms_switch_w
LOAD-02-DEVICE-07 communications switch load
Radio
radio_w
LOAD-02-DEVICE-07 radio load
Point machine heater
point_machine_heater_w
LOAD-02-DEVICE-07 point machine heater load
Spare allowance pct
spare_allowance_pct
UPS-02-DATA-07 spare allowance
Autonomy
autonomy_h
MAINT-02-RESPONSE-07 required backup autonomy
Dc voltage
dc_voltage_v
UPS-02-DATA-07 DC system voltage
Usable battery fraction
usable_battery_fraction
UPS-02-DATA-07 usable battery fraction
Installed battery
installed_battery_ah
UPS-02-DATA-07 installed battery capacity
Feeder length
feeder_length_m
CAB-02-LAYOUT-07 one-way DC feeder length
Conductor resistance milliohm per m
conductor_resistance_milliohm_per_m
CAB-02-LAYOUT-07 conductor resistance
Max voltage drop percent
max_voltage_drop_percent
UPS-02-DATA-07 maximum feeder voltage drop
Fiber length
fiber_length_km
COMMS-02-TOPO-07 fiber link length
Fiber attenuation db per km
fiber_attenuation_db_per_km
COMMS-02-TOPO-07 fiber attenuation
Fiber connector count
fiber_connector_count
COMMS-02-TOPO-07 connector count
Connector loss
connector_loss_db
COMMS-02-TOPO-07 connector loss
Fiber splice count
fiber_splice_count
COMMS-02-TOPO-07 splice count
Splice loss
splice_loss_db
COMMS-02-TOPO-07 splice loss
Patch panel allowance
patch_panel_allowance_db
COMMS-02-TOPO-07 patch-panel allowance
Optical tx power
optical_tx_power_dbm
COMMS-02-TOPO-07 optical transmitter power
Receiver sensitivity
receiver_sensitivity_dbm
COMMS-02-TOPO-07 receiver sensitivity
Required fiber margin
required_fiber_margin_db
COMMS-02-TOPO-07 required optical margin
Selected ups rating
selected_ups_rating_va
UPS-02-DATA-07 selected UPS rating
Load power factor
load_power_factor
UPS-02-DATA-07 UPS load power factor
16 outputs
connected_load_w
Sum of source-owned wayside device loads
Scores if within ±3% of the reference value.
design_load_w
Connected load plus spare allowance
Scores if within ±3% of the reference value.
required_energy_kwh
Design load times autonomy
Scores if within ±3% of the reference value.
required_battery_capacity_ah
Battery amp-hours required after usable fraction
Scores if within ±3% of the reference value.
battery_capacity_margin_ah
Installed battery capacity minus required capacity
Scores if within ±3% of the reference value.
feeder_current_a
DC feeder current at design load
Scores if within ±3% of the reference value.
feeder_voltage_drop_v
Two-wire DC feeder voltage drop
Scores if within ±3% of the reference value.
feeder_voltage_drop_percent
DC feeder voltage drop percentage
Scores if within ±3% of the reference value.
voltage_drop_margin_percent
Maximum allowed voltage drop minus computed voltage drop
Scores if within ±3% of the reference value.
fiber_total_loss_db
Total optical link loss
Scores if within ±3% of the reference value.
fiber_receive_power_dbm
Optical receive power
Scores if within ±3% of the reference value.
fiber_link_margin_db
Receive power minus receiver sensitivity
Scores if within ±3% of the reference value.
fiber_excess_margin_db
Optical link margin above required margin
Scores if within ±3% of the reference value.
required_ups_rating_va
UPS VA required at design load
Scores if within ±3% of the reference value.
ups_rating_margin_va
Selected UPS rating minus required UPS rating
Scores if within ±3% of the reference value.
overall_pass_score
1.0 when battery, feeder, fiber, and UPS margins are non-negative
Scores if within ±0.1% of the reference value.
Each template is sampled at three tiers. Harder tiers may hide inputs, forcing the model to infer them from the scenario description.
For this template, difficulty scales through parameter and scenario ranges rather than hidden information.
The exact instruction and parameter contract used to generate this task, pinned to the published library source.
/workspace
Teal lines show Jinja input conditions, not task visibility policy. A line renders only when that input or tool is visible.
1You are a rail communications and power engineer checking `SSC-02-LH-07`, a task-owned synthetic SSC-02 wayside cabinet load, communications, and backup supply package.2 3Use only the task-owned synthetic source pack values below for numeric grading. Wayside cabinet power, fiber link budget, and backup-power workflows shape the context only; this instance does not parse a real cabinet drawing, network model, or UPS datasheet.4 5## Scene6 7- Design case: `CASE-SSC02-CAB-07`8- Cabinet layout: `CAB-02-LAYOUT-07`9- Device load schedule: `LOAD-02-DEVICE-07`10- Communications topology: `COMMS-02-TOPO-07`11- UPS data sheet: `UPS-02-DATA-07`12- Maintenance response plan: `MAINT-02-RESPONSE-07`13- Resilience memo: `MEMO-02-RESILIENCE-07`14 15## Source Values16 17| Item | Value |18|------|-------|19| Signal processor load | {{ signal_processor_w }} W |20| Axle counter load | {{ axle_counter_w }} W |21| Communications switch load | {{ comms_switch_w }} W |22| Radio load | {{ radio_w }} W |23| Point machine heater load | {{ point_machine_heater_w }} W |24| Spare allowance | {{ spare_allowance_pct }} % |25| Autonomy | {{ autonomy_h }} h |26| DC voltage | {{ dc_voltage_v }} V |27| Usable battery fraction | {{ usable_battery_fraction }} |28| Installed battery capacity | {{ installed_battery_ah }} Ah |29| Feeder length | {{ feeder_length_m }} m |30| Conductor resistance | {{ conductor_resistance_milliohm_per_m }} milliohm/m |31| Maximum voltage drop | {{ max_voltage_drop_percent }} % |32| Fiber length | {{ fiber_length_km }} km |33| Fiber attenuation | {{ fiber_attenuation_db_per_km }} dB/km |34| Connector count | {{ fiber_connector_count }} |35| Connector loss | {{ connector_loss_db }} dB |36| Splice count | {{ fiber_splice_count }} |37| Splice loss | {{ splice_loss_db }} dB |38| Patch panel allowance | {{ patch_panel_allowance_db }} dB |39| Optical transmitter power | {{ optical_tx_power_dbm }} dBm |40| Receiver sensitivity | {{ receiver_sensitivity_dbm }} dBm |41| Required fiber margin | {{ required_fiber_margin_db }} dB |42| Selected UPS rating | {{ selected_ups_rating_va }} VA |43| Load power factor | {{ load_power_factor }} |44 45Checks:46 47- Connected load equals the sum of the five device loads.48- Design load equals connected load times one plus spare allowance.49- Required battery capacity equals `design_load x autonomy / (dc_voltage x usable_fraction)`.50- DC feeder voltage drop uses two-wire length, current, and conductor resistance.51- Fiber link margin uses attenuation, connector loss, splice loss, patch loss, transmitter power, and receiver sensitivity.52- Overall pass score is `1.0` only when battery, feeder, fiber, and UPS margins are non-negative; otherwise it is `0.0`.53 54## Output Format55 56Write a compact memo to `/workspace/output.md`. Preserve the object IDs above, state the task-owned synthetic source-pack boundary, and explain whether the baseline source pack passes the docs-only checks.57 58Do not claim authority approval, accepted project evidence, network model validity, full standards compliance, executable real source-pack parsing, generated benchmark readiness, or benchmark readiness.59 60Include a fenced JSON block with exactly these numeric keys:61 62```json63{64 "connected_load_w": <numeric_value>,65 "design_load_w": <numeric_value>,66 "required_energy_kwh": <numeric_value>,67 "required_battery_capacity_ah": <numeric_value>,68 "battery_capacity_margin_ah": <numeric_value>,69 "feeder_current_a": <numeric_value>,70 "feeder_voltage_drop_v": <numeric_value>,71 "feeder_voltage_drop_percent": <numeric_value>,72 "voltage_drop_margin_percent": <numeric_value>,73 "fiber_total_loss_db": <numeric_value>,74 "fiber_receive_power_dbm": <numeric_value>,75 "fiber_link_margin_db": <numeric_value>,76 "fiber_excess_margin_db": <numeric_value>,77 "required_ups_rating_va": <numeric_value>,78 "ups_rating_margin_va": <numeric_value>,79 "overall_pass_score": <numeric_value>80}81```82 Each generated task is drawn from one of these realistic scenario bands.
Site contexts ground each scenario in a real locale the model can use to infer hidden values.
ssc02_wayside_cabinet_backup_case
Wayside cabinet package tied to one cabinet layout, load schedule, communications topology, UPS data sheet, maintenance response plan, and memo
wayside-cabinet-backup-ssc02-wayside-cabinet-backup-case-preview — hard difficulty, all inputs given.
Wayside cabinet package tied to one cabinet layout, load schedule, communications topology, UPS data sheet, maintenance response plan, and memo. wayside-cabinet-backup. Required outputs: connected_load_w, design_load_w, required_energy_kwh, required_battery_capacity_ah, battery_capacity_margin_ah, feeder_current_a
Scenario context and visible inputs.
Executable tool: wayside-cabinet-load-communications-backup-supply-package_calc.py
Inputs withheld at this difficulty.
Nothing. All inputs are supplied.
The scored JSON answer schema.
{
"connected_load_w": <number>,
"design_load_w": <number>,
"required_energy_kwh": <number>,
"required_battery_capacity_ah": <number>,
"battery_capacity_margin_ah": <number>,
"feeder_current_a": <number>,
"feeder_voltage_drop_v": <number>,
"feeder_voltage_drop_percent": <number>,
"voltage_drop_margin_percent": <number>,
"fiber_total_loss_db": <number>,
"fiber_receive_power_dbm": <number>,
"fiber_link_margin_db": <number>,
"fiber_excess_margin_db": <number>,
"required_ups_rating_va": <number>,
"ups_rating_margin_va": <number>,
"overall_pass_score": <number>
}